  Capacity  
 
 
The UNITAB packages are suitable for cold rooms ranging from 1.5 to 5 kW cooling capacity. The design conditions are for 50°C ambient and -20°C room temperatures.
 
  Coils    
 
The air-cooled condenser and evaporator coils are of staggered type and designed with 3/8” and 5/8” copper tubes, respectively. The evaporator coils are equipped with specially designed refrigerant distributors for optimum performance. The copper tubes are mechanically expanded to have maximum thermal bound with the aluminum fins.
 
  Electro Motors  
 
 
Electro fans have following features :
Axial fans with external rotor motor. Three-phases motor 380/50Hz with internally wired thermal contact. Installation class is B and protection class is IP54.
 
  Electric Board  
 
 
The electric board has the following features:
1
2
3
4
5
 
Adjustable automatic defrost cycle
Adjustable room temperature control
Evaporator fan delay after defrost cycle
High temperature alarm
Adjustable thermodisk temperature for defrost protection
 
  Special Features of Unitab Packages    
 
• Externally equalized thermal expansion valve is used for optimum superheat control.
• The low side refrigerant is pumped down before defrost cycle and compressor shut down.
• The choice of semi hermetic or hermetic compressors.
• Easy to install.
• Requires minimum space for installation.
• Minimum installation cost.
• Low vibration and noise level.
 
  Selection    
 
In order to select a suitable unit for a given cold room the following data must be known.
• Refrigerating capacity.
• Room Temperature.
• Ambient temperature.
To select a unit refer to the “ Quick Selection” table with the above mentioned data and simply select a unit to satisfy the required capacity.
 
  Technical Data    
 
Model Voltage Refri-
gerant
Electric
defrost
heater
Net
weight

Compressor
 

Condenser
 

Evaporator
 
Type  Nominal 
horse-
power 
Fan Nominal
air
volume
Electric
motor
Fan Nominal
air
volume
Air
throw
Electric
motor
Volt-Ph-Hz   watt Kg   HP No×Ømm m3/hr CFM  No×watt  No×Ømm m3/hr CFM m No×watt
UWL2 380-3-50 R22 1875 240 Semi-herm 2 1×400 7815 4600 1×180 1×400 7815 4600 10 1×180
UWL3 380-3-50 R22 1875 280 Semi-herm 3 1×400 7815 4600 1×180 1×400 7815 4600 10 1×180
UWL4 380-3-50 R22 3750 320 Semi-herm 4 2×400 15630 9200 2×180 2×400 15630 9200 10 2×180
UWL5 380-3-50 R22 3750 350 Semi-herm 5 2×450 17160 10100 2×250 2×400 15630 9200 10 2×250
 
 
 
  UWL2    
   
 
  UWL3    
     
Tr
°C
Ta
°C

Capacity

V
m3

kW


kcal/hr


BTU/hr

−25
30 1.76 1513 6005 16
35 1.61 1384 5494 14
40 1.47 1264 5016 12
45 - - - -
50 - - - -
−20
30 2.08 1788 7097 20
35 1.92 1651 6551 17
40 1.77 1522 6039 16
45 1.63 1402 5562 14
50 1.55 1333 5289 12
−15
30 2.56 2201 8735 27
35 2.4 2064 8189 24
40 2.23 1917 7609 21
45 2.07 1780 7063 18
50 1.92 1651 6551 16
−10
30 3.12 2683 10646 31
35 2.93 2519 9998 26
40 2.76 2373 9418 24
45 2.58 2218 8803 20
50 2.41 2072 8223 18
Tr
°C
Ta
°C

Capacity

V
m3

kW


kcal/hr


BTU/hr

−25
30 2.27 1952 7746 24
35 2.11 1814 7200 21
40 1.96 1685 6688 17
45 1.8 1548 6142 16
50 1.68 1445 5732 14
−20
30 2.08 2408 9554 34
35 2.63 2261 8974 30
40 2.44 2098 8326 26
45 2.28 1960 7780 22
50 2.14 1840 7302 19
−15
30 3.42 2941 11670 46
35 3.21 2760 10953 41
40 3 2580 10236 37
45 2.83 2433 9556 32
50 2.69 2313 9179 26
−10
30 4.09 3517 13956 64
35 3.86 3319 13171 62
40 3.65 3138 12454 57
45 3.43 2949 11704 54
50 3.3 2837 11260 50
 
 
  UWL4    
  UWL5  
 
 
Tr
°C
Ta
°C

Capacity

V
m3

kW


kcal/hr


BTU/hr

−25
30 3.43 2949 11704 54
35 3.2 2752 10919 48
40 2.98 2562 10168 43
45 2.75 2365 9383 37
50 2.54 2184 8667 32
−20
30 4.19 3603 14297 70
35 3.92 3371 13376 62
40 3.68 3164 12557 58
45 3.45 2966 11772 52
50 3.19 2743 10885 48
−15
30 5.02 4316 17129 94
35 4.76 4093 16242 86
40 4.47 3844 15252 77
45 4.22 3629 14399 70
50 3.93 3379 13410 65
−10
30 6 5159 20473 114
35 5.67 4875 19347 100
40 5.36 4609 18289 90
45 5.08 4368 17334 84
50 4.77 4101 16276 80
Tr
°C
Ta
°C

Capacity

V
m3

kW


kcal/hr


BTU/hr

−25
30 5.3 4557 18084 93
35 5.02 4316 17129 84
40 4.73 4067 16139 76
45 4.45 3826 15184 67
50 4.18 3594 14263 58
−20
30 6.37 5477 21735 120
35 6.05 5202 20643 109
40 5.75 4944 19620 99
45 5.44 4678 18562 89
50 5.11 4394 17436 78
−15
30 7.58 6518 25864 152
35 7.19 6182 24533 140
40 6.85 5890 23373 130
45 6.51 5598 22213 118
50 6.14 5279 20951 105
−10
30 8.95 7696 30539 178
35 8.51 7317 29037 170
40 8.1 6965 27638 160
45 7.72 6638 26342 145
50 7.28 6260 24840 132
  Tr: Cold room Temp.  
  Ta: Ambient Temp.  
 
  V: Cold room Valume  
 
 
 
 
 
 
 
 
 
  Roughing Dimensions(cm)    
 Model A B C D E F G H I J K
 UWL2  1900 700 150 700 700 950 630 1110 710 960 1"
 UWL3  1900 700 150 700 700 950 630 1110 710 960 1"
 UWL4  1900 700 150 700 700 1250 630 1410 710 1260 1"
 UWL5  1900 700 150 700 700 1600 630 1760 710 1610 1"